Interface Specifications IDEC Web Server Module Part Number Description Communication RS232C <=> Ethernet conversion function Ethernet Specifications Electrical characteristics: Complies with IEEE802.3 Transmission speed: 10BASE-T/100BASE-TX (Not CE compliant) Communication protocol: IP/ICMP/ARP Ethernet protocol: TCP/SMTP/HTTP/Telnet No. of TCP connections: 1 Serial I/F Specifications Electrical characteristics: Transmission speed: Synchronization: Communication protocol: Transmission control: EIA RS232C 9600 to 115200 bps Asynchronous Full duplex RTS/CTS, XON/OFF, None Ethernet interface: Serial interface: RJ45 Mini DIN 8-pin connector Cable Type No.: FC4A-KC3C Remote maintenance: Uploading, downloading and monitoring using WindLDR via Ethernet Web Server module including interface cable, manual on CD-ROM and Quick Start guide FC4A-ENET General Specifications Rated Power Voltage 24V DC Allowable Voltage Range 20.4 to 26.4V DC Current Draw 70mA Allowable Momentary Power Interruption 10ms maximum Dielectric Strength 500V AC, 1 minute Insulation Resistance 10M minimum (500V DC megger) Noise Resistance DC power terminal: 1.0kV, 50ns to 1s Ethernet cable: 0.5kV, 50ns to 1s (coupling clamp) Inrush Current 4A maximum Operating Temperature 0 to 55C Storage Temperature -40 to +70C (no freezing) Relative Humidity 10 to 95% (no condensation) Pollution Degree 2 (IEC 60664-1) Corrosion Immunity Free from corrosive gases Degree of Protection IP20 (IEC60529) Vibration Resistance When mounted on a DIN rail: 5 to 9Hz amplitude 3.5 mm 9 to 150Hz accelaration 9.8m/s2 (1G) 2 hours in each of 3 axes Shock Resistance 147m/s2 (15G), 11ms duration 3 shocks each in 3 axes Weight (approx.) Connection Method Major Functions Monitor, Control and Maintain Production From Anywhere Web server: Configure the web server unit using Internet Explorer etc. Reading and writing PLC operands using Java applet. Web file area: 512 Kbyte Compliant browser: Internet Explorer 6.0 Netscape 7.2 Data Exchange: User communication using Ethernet Alarm Messaging: Registered outgoing message 32 message types 3 characters max. 2 email addresses 64 address characters max. Option 150g Utility CD: Configuration file, PLC operand monitor sample programs, sample program configuration instructions, instruction manual Specifications and other descriptions in this catalog are subject to change without notice. Dimensions **Mounting Hole Layout for Direct Mounting 80.0 2.1 45.0 35.0 Connectable Devices 70.0 80.0 70.0 45.0 5.6mm when the clamp is pulled out **Programmable Controllers IDEC FC5A MicroSmart (available soon) IDEC FC4A MicroSmart IDEC FC3A OpenNet Controller IDEC FC2A Micro3C **Operator Interface (RS232C communication with PLC through Ethernet) IDEC HG2F M4 mounting screw (12 mm or 15 mm) www.idec.com 1-800-262-IDEC (c)2006 IDEC Corporation. All Rights Reserved. Catalog No. FC9Y-B200-0 17.5k 4/06 IDEC Web Server Module Save Time and Experience Faster, Easier Ethernet Connectivity Remote Maintenance O/I Connectivity * Easily monitor machine conditions, change machine configurations, or upload and download user programs from anywhere, using IDEC WindLDR software over an Ethernet network. * Using the IDEC Web Server Module on an Ethernet network, an IDEC PLC can be configured as a host to an IDEC operator interface. This allows the touchscreen and PLC to be in separate locations. * For a more graphical display and remote data archiving, OPC servers, such as IDEC WindSRV or standard SCADA software, can be used. * Save time and money: - Access system parameters from your desk, conference room or home to check machine status without walking the factory floor. If a machine is down, you no longer need to send someone with their laptop to debug or download a new user program. * No longer hassle with specialized cables and serial connection limitations. Ethernet Ethernet Data Exchange Web Monitoring FC4A-ENET * Machine status can be monitored and controlled from any PC using standard internet browsers such as Internet Explorer or Netscape(R). Ethernet * A built-in custom template, which allows you to monitor and change system parameters, is included. * Get more flexibility and control by creating your own custom templates - for monitoring and managing your system - using JAVA programming. Alarm Messaging * Real-time updates of error status or process conditions can be sent to an email address or cellular phone. * A maximum of 32 customizable messages can be predefined with up to two email addresses each. ID JSmith Password ********* Password Protection * The IDEC Web Server Module can be configured with password protection to allow only authorized personnel to gain access to your system. * An IDEC PLC can transmit and receive data with external devices - IDEC PLCs, operator interfaces, or other devices - in 1:1 format.