IDEC
Web Server Module
General Specifications
Rated Power Voltage 24V DC
Allowable Voltage Range 20.4 to 26.4V DC
Current Draw 70mA
Allowable Momentary
Power Interruption 10ms maximum
Dielectric Strength 500V AC, 1 minute
Insulation Resistance 10MΩ minimum (500V DC megger)
Noise Resistance DC power terminal: 1.0kV, 50ns to 1µs
Ethernet cable: 0.5kV, 50ns to 1µs (coupling clamp)
Inrush Current 4A maximum
Operating Temperature 0 to 55˚C
Storage Temperature –40 to +70˚C (no freezing)
Relative Humidity 10 to 95% (no condensation)
Pollution Degree 2 (IEC 60664-1)
Corrosion Immunity Free from corrosive gases
Degree of Protection IP20 (IEC60529)
Vibration Resistance
When mounted on a DIN rail:
5 to 9Hz amplitude 3.5 mm
9 to 150Hz accelaration 9.8m/s2 (1G)
2 hours in each of 3 axes
Shock Resistance 147m/s2 (15G), 11ms duration
3 shocks each in 3 axes
Weight (approx.) 150g
Interface Specifications
Communication RS232C <=> Ethernet conversion function
Ethernet
Specifications
Electrical characteristics: Complies with IEEE802.3
Transmission speed: 10BASE-T/100BASE-TX
(Not CE compliant)
Communication protocol: IP/ICMP/ARP
Ethernet protocol: TCP/SMTP/HTTP/Telnet
No. of TCP connections: 1
Serial I/F
Specifications
Electrical characteristics: EIA RS232C
Transmission speed: 9600 to 115200 bps
Synchronization: Asynchronous
Communication protocol: Full duplex
Transmission control: RTS/CTS, XON/OFF, None
Connection
Method
Ethernet interface: RJ45
Serial interface: Mini DIN 8-pin connector
Cable Type No.: FC4A-KC3C
Major
Functions
Remote maintenance: Uploading, downloading and
monitoring using WindLDR via
Ethernet
Web server: Configure the web server unit using
Internet Explorer etc. Reading and writing
PLC operands using Java applet.
Web file area: 512 Kbyte
Compliant browser: Internet Explorer 6.0
Netscape 7.2
Data Exchange:
User communication using Ethernet
Alarm Messaging:
Registered outgoing message
32 message types
3 characters max.
2 email addresses
64 address characters max.
Dimensions
Option
Utility CD: Configuration file, PLC operand monitor sample
programs, sample program configuration
instructions, instruction manual
Connectable Devices
Programmable Controllers
•
IDEC FC5A MicroSmart (available soon)
IDEC FC4A MicroSmart
IDEC FC3A OpenNet Controller
IDEC FC2A Micro3C
Operator Interface
•
(RS232C communication with PLC through Ethernet)
IDEC HG2F
Specifications and other descriptions in this catalog are subject to change without notice.
Mounting Hole Layout
• for Direct Mounting
45.0
80.0
2.1
45.0
35.0
70.0
80.0
70.0
∗
∗5.6mm when the clamp is pulled out
M4 mounting screw
(12 mm or 15 mm)
www.idec.com
1-800-262-IDEC
©2006 IDEC Corporation. All Rights Reserved.
Catalog No. FC9Y-B200-0 17.5k 4/06
Part Number Description
FC4A-ENET Web Server module including interface cable, manual
on CD-ROM and Quick Start guide
IDEC Web Server Module
Monitor, Control and Maintain
Production From Anywhere