Analogue Temperature Controller E5C2 I-7
Temperature
Controller
Analogue Temperature Controller
E5C2
DIN-sized (48 x 48 mm) Temperature
Controller with Analog Setting
Compact, low-cost Temperature Controller.
Incorporates proportional control and reset adjustment function.
Consecutive mounting possible using mounting adapter.
Incorporates a plug-in socket, thus allows to DIN-track and flush
mounting.
®
Model Number Structure
Model Number Legend
1. Model name
2. Control output
R: Relay
Q: Voltage
3. Control method
20: ON-OFF control
40: P control
4. Input type
K: K-type thermocouple
L: J-type thermocouple
P: Platinum resistance thermometer (PT100)
G: Thermistor (THE)
5. Special type
Blank: Standard type
D, DIN: Special types
Ordering Information
Temperature Controllers
Note: When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C2-R20K 0°C to 200°C100/110 VAC)
Accessories (Order Separately)
12345
E5C2- @ @ @ @
Setting
method Indication
method Control mode Output Model
Thermocouple Platinum resistance
thermometer
Pt100
Thermistor
THE
K (CA)
Chromel vs.
alumel
L (IC)
Iron vs.
constantan
Analog setting No indication ON/OFF Relay E5C2-R20K
E5C2-R20L-D
E5C2-R20P-D E5C2-R20G
P Relay E5C2-R40K
E5C2-R40L-D
E5C2-R40P-D ---
Name Model
Front Connecting Socket P2CF-08
Back Connecting Socket (for flush mounting) P3G-08
Front Connecting Socket with Finger Protection P2CF-08-E
Protective Cover (for finger protection) Y92A-48G
I-8 Analogue Temperature Controller E5C2
Specifications
Ratings
Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
Input Ranges
Note: 1. Values in ( ) are the minimum unit.
2. Values in ( ) are the thermistor resistive value.
Characteristics
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Supply voltage 100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
50/60 Hz (common)
Operating voltage range 90% to 110% of rated supply voltage
Power consumption Approx. 2 VA
Input Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor
Control mode ON/OFF or P control
Setting method Analog setting
Indication method No indication
Control output Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Input Thermocouple Platinum resistance
thermometer Thermistor (see note 2)
K (CA)
Chromel vs. alumel L (IC)
Iron vs. constantan Pt100 THE
Range °C0 to 200 (5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
–50 to 50 (2),
–20 to 80 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
–50 to 50 (2) (6 k at 0°C),
0 to 100 (2) (6 k at 0°C),
50 to 150 (2) (30 k at 0°C)
°F32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20)
32 to 212 (5),
32 to 392 (10)
---
Setting accuracy ±2% FS max.
Hysteresis Approx. 0.5% FS (fixed)
Proportional band 3% FS (fixed)
Control period Approx. 20 s
Reset range (see note 1) 5 ±1% FS min.
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Vibration resistance Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 147 m/s2, 3 times each in 6 directions
Destruction: 294 m/s2, 3 times each in 6 directions
Life expectancy Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load)
Ambient temperature Operating: –10°C to 55°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Degree of protection Front panel: IEC standard IP40 (see note 2)
Terminals: IEC standard IP00
Weight Approx. 200 g (with flush-mounting adapter)
Analogue Temperature Controller E5C2 I-9
Temperature
Controller
Nomenclature
Operation Indicator
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Temperature setting knob
Operation indicator
RESET adjustment shaft
No reset function is incorporated by any
E5C2 model with ON/OFF control.
Indicator Output
Red Lit ON
Not lit OFF
93+1
0 141+1
0 189+1
0 237+1
0 285+1
0
N23456
L
48 x 48
44.8 x 44.8
Panel Cutout
Note: 1. Recommended panel thickness is 1 to 4 mm.
2. Close side-by-side mounting is possible (in a single direction).
Panel
Y92F-30 Flush-mounting adapter
Tightening screw
(96) (see note)
Note: 109 mm for US08 Back Connecting Socket
Terminal Arrangement
(Bottom View)
Dimensions with Flush-mounting Adapter (Accessory),
and Back Connecting Socket (Sold Separately)
Flush-mounting
adapter P3G-08 Back con-
necting socket
Side-by-side Mounting
of N Controllers
60 min.
I-10 Analogue Temperature Controller E5C2
Accessories (Order Separately)
Protective Cover Y92A-48
The protective cover protects the front panel, particularly the setting
section, against dust, dirt, and water drip. It also prevents the set val-
ues from being altered due to accidental contact with the setting
keys.
Installation
Connections
Input
Connect a thermocouple, the E52-THE@ Thermistor or platinum
resistance thermometer to the E5C2 as shown in the following illus-
tration.
Output
If the load circuit is a heating control system, be sure to connect the
load to terminals 4 and 5. If the load circuit is a cooling control sys-
tem, be sure to connect the load to terminals 4 and 6. If the heating
control system is connected to terminals 4 and 6 or the cooling con-
trol system is connected to terminals 4 and 5, the temperature of the
heating control system or cooling control system will be abnormal
and a serious accident may result.
If the E5C2 is in frequent operation, such as proportional operation,
add an appropriate external relay to the E5C2 by considering the
capacity of the load and the life of the relay.
Power Supply
If a single power supply is used for the E5C2 and the load, the supply
voltage of the power supply may vary greatly when the load is open
or closed if the capacity of the power supply is not large enough.
Make sure that the capacity of the power supply is large enough so
that the supply voltage range will be always from 90% to 110% of the
rated supply voltage.
The E5C2 operates at either 50 or 60 Hz.
P2CF-08 Front Connecting Socket
Mounting Holes
70 max.
Eight, M3.5 x 7.5 sems
50 max.
20 max.
Two, 4.5 dia. or Two, M4
P3G-08 Back Connecting Socket (for Flush Mounting)
27 dia.
Two,
4.5-dia.
holes
Terminal Arrangement/
Internal Connections
(Top View)
Note: Can also be
mounted to a
DIN track.
Terminal Arrangement/
Internal Connections
(Bottom View)
Note: A finger-protection model (P2CF-08-E) is also available.
Note: A Protective Cover for fin
g
er
p
rotection
(
Y92A-48G
)
is also available.
Appearance
Model Y92A-48B
Thermocouple input
Relay output
Thermistor input
Platinum resistance
thermometer input
Power supply
100/110, 200/220,
110/120, 220/240 VAC
50/60 Hz
Analogue Temperature Controller E5C2 I-11
Temperature
Controller
Precautions
Mounting
Track Mounting (E5C2 with P2CF-08)
When mounting two or more E5C2 models with track-mounting sock-
ets, leave a space of approximately 20 mm on both sides of the sock-
ets where hooks are located.
Flush Mounting
Insert E5C2 into the square hole of the panel and insert an adapter
from the back so that there will be no space between E5C2 and the
panel. Then, secure the E5C2 with a screw.
The P3G-08 can be wired in the same way as the P2CF-08.
Dismounting
If flush mounted, loosen the screw of the adapter and disengage the
hooks for dismounting.
Temperature Setting
Do not turn the temperature setting knob of the E5C2 with excessive
force, otherwise the stopper of the knob may break.
Others
Do not remove the housing of the E5C2, otherwise the housing may
break.
To clean the surface of the E5C2, use a soft cloth wet with neutral
detergent or alcohol. Do not use any organic solvent, such as paint
thinner or benzine, strong acid or strong alkali to clean the surface of
the E5C2, otherwise the surface of the E5C2 will become damaged.
20
P2CF-08
Panel
Hook
Duct
Tightening screw
I-12 Analogue Temperature Controller E5C2
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H081-E1-02