Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
40
1Power Protection and Conditioning
The STC-CCTV Series is tailored specically to CCTV, data,
audio and cable applications. These units are single Coax
Surge Protective Devices implementing three-stage hybrid
technology. They address overvoltage transients with
a primary gas tube, and secondary silicon avalanche
components. Over-currents (e.g. sneak and fault currents)
are mitigated with solid-state resetable fuses (PTCs). The
STC-CCTV units are designed in accordance with NFPA
780 (2004 Edition) requirements, with up to 20kA of surge
current capability. The STC-CCTV-75I model has an isolated
ground and is recommended for use at the camera end.
Applications
• CCTV Head End
• CCTV Camera End
Features
• Hybrid, three-stage technology
• Sneak/fault current protection
• Low insertion loss
• Shielded case
• Five year limited warranty
Certifications and Compliances
Listed
- UL 497B
• RoHS Compliant
• NFPA 780 (2004) Compliant for Communication
Protectors
STC-CCTV Coax Series
Specifications
Description STC-CCTV-75 STC-CCTV-75I
Operating Voltage 5
Clamping Voltage 6
Frequency Range 0 to 20 MHz
Equipment Location IEEE Category C, and Category B
Rated Load Current 0.35 amperes
Topology 2-port Series
STC Technology
Primary Stage: Gas Tubes,
Secondary Stage: Silicon Avalanche Components
Third Stage: resetable fuses (PTCs)
Modes of Protection Signal to Ground
Nominal Discharge
Current per Mode 10.0 kA
Maximum Discharge
Current per Mode 20.0 kA
EMI Attenuation < 0.1 dB at 20 MHz
VSWR < 1.2
Continuous Power 0.72 Watts
Operating Humidity 0-95 % Non-condensing
Operating & Storage
Temperature -40oC to +85oC
Input & Output
Connection Type BNC, 50/75 Ohm
Mounting Flange
Enclosure Type Metal
Warranty 5 year limited warranty
Catalog Number Description
STC-CCTV-75 Without isolated ground
STC-CCTV-75I With isolated ground
Selection Table