For more Information
please call
1-800-Belden1
General Description:
16 AWG pairs stranded (7x24) bare copper conductors, twisted pairs, overall Beldfoil shield (100%
coverage), PVC insulation, PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Pairs AWG Stranding Conductor Material
116 7x24 BC - Bare Copper
Total Number of Conductors: 2
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.4064
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
18 7x26 TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 0.9398
Outer Jacket Ripcord: Yes
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1Black & White
Overall Nominal Diameter: 6.528 mm
Pair
Pair Lay Length & Direction:
Lay Length (mm) Twists (twist/m)
76.200 13.124
Mechanical Characteristics (Overall)
Operating Temperature Range: -30°C To +105°C
Bulk Cable Weight: 62.951 Kg/Km
Max. Recommended Pulling Tension: 177.928 N
Min. Bend Radius/Minor Axis: 66.040 mm
Page 1 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
1030A Multi-Conductor - 300V Power-Limited Tray Cable
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: ITC, PLTC
CEC/C(UL) Specification: CMG
AWM Specification: UL Style 2464 (300 V 80°C)
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Flame Test
UL Flame Test: UL1685 FT4 Loading
CSA Flame Test: FT4
IEEE Flame Test: 1202
Suitability
Sunlight Resistance: Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Surface Printing (Overall)
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/m)
0.62339
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
200.141
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
374.034
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
12.1397
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
16.7331
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
11 Amps per conductor @ 25°C
Page 2 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
1030A Multi-Conductor - 300V Power-Limited Tray Cable
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
1030A 0061000 305 MT 20.412 KG BLUE, LIGHT C 2 #16 PVC FS PVC
1030A 00610000 3,048 MT 213.189 KG BLUE, LIGHT C 2 #16 PVC FS PVC
1030A 0065000 1,524 MT 99.791 KG BLUE, LIGHT 2 #16 PVC FS PVC
1030A 0101000 305 MT 20.865 KG BLACK C 2 #16 PVC FS PVC
1030A 01010000 3,048 MT 217.725 KG BLACK C Z 2 #16 PVC FS PVC
1030A 0105000 1,524 MT 102.059 KG BLACK C Z 2 #16 PVC FS PVC
Notes:
C = CRATE REEL PUT-UP.
Z = FINAL PUT-UP LENGTH MAY VARY (+ OR -) 10% FOR SPOOLS OR REELS AND(+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
Revision Number: 2 Revision Date: 07-20-2012
© 2013 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the
compliance date may be in stock at Belden facilities and in our Distributor’s inventory. The information provided in this Product Disclosure, and
the identification of materials listed as reportable or restricted within the Product Disclosure, is correct to the best of Belden’s knowledge,
information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide
for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not
to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for
determining the applicability of legislation and regulations based on their individual usage of the product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 73/23/EEC), as amended by directive 93/68/EEC.
Page 3 of 3 10-30-2013
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
1030A Multi-Conductor - 300V Power-Limited Tray Cable