Digital Controller IE5AK
Advanced Digital Controllers Ideal for
Worldwide Use IE5_K
Modular structure, one-stock type
High-accuracy: 100 ms sampling (for analog input)
Advanced tuning which includes fuzzy self-tuning
Conforms to international EMC and safety
standards.
IP66/NEMA4 (indoor use) front face
Remote set point
Serial communications (RS-232C, RS-422 and
RS-485) and transfer output (4 to 20 mA)
Position-proportional control model
Heat/Cool control
AC/DC24V types are also available.
Ordering Information
Description Model Specification
Base Unit E5AK-AA2 AC100-240 Standard model
E5AK-AA2-500 AC100-240 Standard model with terminal cover
E5AK-AA2 AC/DC24 Standard model
E5AK-AA2-500 AC/DC24 Standard model with terminal cover
E5AK-PRR2 AC100-240 Position-proportional model
E5AK-PRR2-500 AC100-240 Position-proportional model with terminal cover
E5AK-PRR2 AC/DC24 Position-proportional model
E5AK-PRR2-500 AC/DC24 Position-proportional model with terminal cover
E5EK-AA2 AC100-240 Standard model
E5EK-AA2-500 AC100-240 Standard model with terminal cover
E5EK-AA2 AC/DC24 Standard model
E5EK-AA2-500 AC/DC24 Standard model with terminal cover
E5EK-PRR2 AC100-240 Position-proportional model
E5EK-PRR2-500 AC100-240 Position-proportional model with terminal cover
E5EK-PRR2 AC/DC24 Position-proportional model
E5EK-PRR2-500 AC/DC24 Position-proportional model with terminal cover
Note: 1. When using the heater burnout alarm function with a standard model, the Linear Output Unit cannot be used for the control outputs
(heat).
2. Be sure to specify the Current Transformer, Output Unit, and Option Unit when ordering.
3. The Digital Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at 4 to 20 mA for the
current outputs.
E5AK E5AK
2
Description Model Specification
Output Unit E53-R Relay
E53-R SSR
E53-Q Pulse (NPN) 12 VDC
E53-Q3 Pulse (NPN) 24 VDC
E53-Q4 Pulse (PNP) 24 VDC
E53-C3 Linear (4 to 20 mA)
E53-C3D Linear (0 to 20 mA)
E53-V34 Linear (0 to 10 V)
E53-V35 Linear (0 to 5 V)
Note: The Digital Controller uses a dedicated, high-resolution Output Unit. The E53-C Current Output Unit for the E5jX cannot be used with
the Digital Controller.
Description Model Specification
Option Unit E53-AKB Event input
E53-AK01 Communication (RS-232C)
E53-AK02 Communication (RS-422)
E53-AK03 Communication (RS-485)
E53-AKF T ransfer output
Note: 1. The Option Unit can be used either by the E5AK or E5EK.
2. The E5AK allows a maximum of three Option Units to be mounted. Refer to page 7 for mounting combinations.
The E5EK allows only one Option Unit to be mounted.
Inspection Report
The Digital Controller can be provided together with an inspection report.
Refer to the following legend with the suffix “K” when ordering a model provided together with an inspection report.
E5jK-AA2-K, E5jK-PRR2-K, E53-AKF-K
Accessories (Order Separately)
Name Model Hole diameter
Current Transformer E54-CT1 5.8 mm
E54-CT3 12.0 mm
Note: No CT is required unless the heater burnout alarm function is used.
Name Model Connectable models
Terminal Cover E53-COV0809 E5AK
E53-COV08 E5EK
Ranges
Platinum Resistance Thermometer
Input (switch selectable) JPt100 Pt100
Range °C–199.9 to 650.0 –199.9 to 650.0
°F–199.9 to 999.9 –199.9 to 999.9
Setting 0 1
Thermocouple
Input (switch
selectable)
(see note)
K1 K2 J1 J2 T E L1 L2 U N R S B W PLII
Range °C–200
to
1,300
0.0 to
500.0 –100
to
850
0.0 to
400.0 –199.9
to
400.0
0 to
600 –100
to
850
0.0 to
400.0 –199.9
to
400.0
–200
to
1,300
0 to
1,700 0 to
1,700 100
to
1,800
0 to
2,300 0 to
1,300
°F–300
to
2,300
0.0 to
900.0 –100
to
1,500
0.0 to
750.0 –199.9
to
700.0
0 to
1,100 –100
to
1,500
0.0 to
750.0 –199.9
to
700.0
–300
to
2,300
0 to
3,000 0 to
3,000 300
to
3,200
0 to
4,100 0 to
2,300
Setting 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Note: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
E5AK E5AK
3
Current/Voltage
Input (switch selectable) Current input Voltage input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Range One of following ranges depending on results of scaling
–1999 to 9999
–199.9 to 999.9
–19.99 to 99.99
–1.999 to 9.999
Setting 17 18 19 20 21
Specifications
Ratings
Item AC100-240V type AC/DC24V type
Supply voltage AC100–240V~, 50/60 Hz AC/DC24V~, 50/60 Hz
Power consumption E5AK: 16 VA
E5EK: 15 VA 12 VA, 8 W
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input: 4 to 20 mA, 0 to 20 mA (Input impedance: 150 )
Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V (Input impedance: 1 M)
Control output Standard Model
According to Output Unit (see
“Output Unit Ratings and Characteristics”
)
Position-proportional Model
2 Relay outputs: SPST-NO, 1 A at 250 VAC (including inrush current) (see note 1)
Auxiliary output SPST-NO, 3 A at 250 VAC (resistive load)
Control method (see note 2) ON/OFF or advanced PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and LEDs
Potentiometer 100 to 2.5 k
Event input Contact input: ON: 1 k max., OFF: 100 k min.
No-contact input: ON: residual voltage: 1.5 V max., OFF: leakage current: 0.1 mA max.
T ransmission output 4 to 20 mA, permissible load impedance: 600 max., resolution: approx. 2,600
Remote SP input Current input: 4 to 20 mA (Input impedance: 150 )
Current Transformer input Connect an exclusive Current T ransformer (E54-CT1 or E54-CT3)
Other functions Standard
Manual output, heating/cooling control, SP limiter, loop burnout alarm, SP ramp, MV limiter ,
MV change rate limiter, input digital filter, input shift, run/stop, protect functions
Option
Multiple SP, run/stop selection, transfer output functions
Enclosure ratings Conforms to IEC IP66 and NEMA4 (Indoor use)
Note: 1. All control outputs are insulated from the input circuit.
2. Fuzzy self-tuning is available when using the Digital Controller in standard control operation with temperature input.
E5AK E5AK
4
Characteristics
Indication accuracy (see note 1) Thermocouple:
(±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input: ±0.2% FS ±1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range –1,999 to 9,999 or –199.9 or 999.9 (decimal point position dependent on input type or result of
scaling)
Sampling period (see note 2) Temperature input: 250 ms
Analog input: 100 ms
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s2 (approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s2 (approx. 2G) for 2 hrs each in X, Y, and Z directions
Shock resistance Malfunction: 200 m/s2 min. (approx. 20G), 3 times each in 6 directions
(100 m/s2 (approx. 10G) applied to the relay)
Destruction: 300 m/s2 min. (approx. 30G), 3 times each in 6 directions
Ambient temperature Operating: –10°C to 55°C (with no icing)/3-year warranty period: –10°C to 50°C
Storage: –25°C to 65°C (with no icing)
Ambient humidity Operating: 35% to 85%
Enclosure ratings Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight E5AK: approx. 450 g
E5EK: approx. 320 g
Mounting bracket: approx. 65 g
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal
cover is mounted.
Note: 1. The indication accuracy of the K1, T , and N thermocouples at a temperature of -100°C or less is ±2°C ±1 digit maximum. The indica-
tion accuracy of the U, L1, and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is greater)
±1 digit maximum.
The indication accuracy of the PLII thermocouple at any temperature is (±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
2. The sampling period of the standard model with CT and remote SP inputs is 1 s.
E5AK E5AK
5
Output Unit Ratings and Characteristics
Relay output 5 A at 250 VAC (resistive load)
SSR output 1 A at 75 to 250 VAC (resistive load)
Voltage output NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
Linear current output 4 to 20 mA, permissible load impedance: 600 max., resolution: approx. 2,600
0 to 20 mA, permissible load impedance: 600 max., resolution: approx. 2,600
Linear voltage output 0 to 10 VDC, permissible load impedance: 1 k max., resolution: approx. 2,600
0 to 5 VDC, permissible load impedance: 1 k max., resolution: approx. 2,600
Note: An output relay (1 A at 250 VAC) is mounted on the position-proportional model. (When replacing, use the E53-R.)
Option Unit Ratings and Characteristics
Event inputs Contact input:
ON: 1 k max., OFF: 100 k min.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
Communications Interface: RS-232C, RS-422 or RS-485
T ransmission method: Half-duplex
Synchronization method: Start-stop synchronization (asynchronous method)
Baud rate: 1.2/2.4/4.8/9.6/19.2 kbps
Transfer output 4 to 20 mA:
Permissible load impedance: 600 max.
Resolution: approx. 2,600
Current Transformer Ratings
Dielectric strength 1,000 VAC (for 1 min)
Vibration resistance 50 Hz, 98 m/s2 (10G)
Weight E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Accessories (E54-CT3 only) Armature: 2; Plug: 2
Heater Burnout Alarm
Max. heater current Single-phase 50 A VAC (see note 1)
Heater current value display accuracy ±5% FS±1 digit max.
Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) (see note 2)
Min. detection ON time 190 ms (see note 3)
Note: 1. Use the K2CU-FjjA-jGS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
E5AK E5AK
6
Nomenclature
E5AK
E5EK
Operation Indicators
OUT1
Lit when the pulse output function
assigned to control output 1 turns
ON.
OUT2
Lit when the pulse output function
assigned to control output 2 turns
ON.
SUB1
Lit when the output function
assigned to auxiliary output 1
turns ON.
SUB2
Lit when the output function
assigned to auxiliary output 2
turns ON.
MANU
Lit when the manual operation
mode.
STOP
Lit during operation has stopped.
RMT
Lit during remote operation.
AT
Flashes during auto-tuning.
RSP
Lit during remote SP operation.
Bar Graph
On a standard model (E5AK-
AA2), this bar graph indicates the
manipulated variable (heat) in
10% increments per single seg-
ment. On a position-proportional
model (E5AK-PRR2), this bar
graph indicates the valve opening
in 10% increments per single
segment.
A/M Key
Press to select the auto operation or
manual operation.
No. 1 Display
Displays the process value or pa-
rameter symbols.
No. 2 Display
Displays the set point, manipulated
variable, or parameter settings.
Up Key/Down Key
Press to increase or decrease the
value on the No.2 display.
Display Key
Press for less than 1 s to shift the
display to the next parameter. When
this key is pressed for 1 s or more,
the menu screen will be displayed in
any case.
A/M Key
Display Key
No. 1 display
No. 2 display
Operation indicators
Up Key/Down Key
E5AK E5AK
7
Operation
Note: Always turn off the power supply to the Digital Controller before changing any switch settings.
Settings
On a standard model, set up the Output Units for control outputs 1
and 2 before mounting the Controller.
On a position-proportional model, the Relay Output Unit is already
set. Therefore, this setup operation is unnecessary. (Do not replace
with other Output Units.)
When setting up the Output Units, draw out the internal mechanism
from the housing and insert the Output Units into the sockets for
control outputs 1 and 2.
Setting Up the Output Unit
Removing the Output Unit
To replace the Output Unit, use a flat-blade screwdriver to push up
the Output Unit.
Setting Up the Option Unit
E5AK
1. Remove the power board and option boards in the order
shown in the following diagram.
2. Insert the Option Units into the sockets for options 1 to 3. The
following diagram shows the relationship between the Option
Units and mounting positions.
3. Mount the option boards and the power board in the order
shown.
E5AK E5AK
8
E5EK
1. Remove the power board and option boards in the order
shown in the following diagram.
2. Insert the Option Unit into the socket for option 1. The
following diagram shows the relationship between the Option
Unit and mounting position.
3. Mount the option board and the power board in the order
shown.
Draw-out
T o draw out the internal mechanism from the housing, use a Phillips
screwdriver matching the screw on the lower part of the front panel.
1. T urn the screw counterclockwise while pressing the hook on
the upper part of the front panel.
Hook
2. Draw out the internal mechanism while holding the left and
right sides of the front panel.
Mounting
1. Insert the E5AK Controller into the panel’s mounting hole at
the position shown in the figure below.
2. Fit the mounting bracket (accessory) into the fixing slots on
the top and bottom of the rear case.
3. T ighten the mounting bracket screws on the upper and lower
parts of the E5AK in small increments alternately and equally
until the ratchet start to slide.
E5AK E5AK
9
E53-COV0809, E53-COV08 Terminal Cover (Sold Separately)
Fasten the terminals covers as follows by using the snap pins. Snap
pins are provided with the terminal covers.
E5AK E5AK
10
After Turning Power ON
Determine the I/O specifications of the Digital Controller in setup
mode.
Power ON
Process value
1 s min.
1 s min.
Input type
Temperature input Current/Voltage input
°C/°F
selection
Scaling
upper limit
Scaling
lower limit
Decimal point
Parameter initialize
From next page To next page
Input Type
Set the code according to the following table. Default is “2: K1 ther-
mocouple.”
Platinum Resistance Thermometer
Set In
p
ut t
yp
e
Set
value
Inp
u
t
type
0JPt100 –199.9 to 650.0 (°C)
/–199.9 to 999.9 (°F) Platinum
resistance
th t
1Pt100 –199.9 to 650.0 (°C)
/–199.9 to 999.9 (°F)
resistance
thermometer
2K1 –200 to 1,300 (°C)
/–300 to 2,300 (°F) Thermocouple
3K2 0.0 to 500.0 (°C)
/0.0 to 900.0 (°F)
4J1 –100 to 850 (°C)
/–100 to 1,500 (°F)
5J2 0.0 to 400.0 (°C)
/0.0 to 750.0 (°F)
6T –199.9 to 400.0 (°C)
/–199.9 to 700.0 (°F)
7E 0 to 600 (°C)
/0 to 1,100 (°F)
8L1 –100 to 850 (°C)
/–100 to 1,500 (°F)
9L2 0.0 to 400.0 (°C)
/0.0 to 750.0 (°F)
10 U –199.9 to 400.0 (°C)
/–199.9 to 700.0 (°F)
11 N –200 to 1,300 (°C)
/–300 to 2,300 (°F)
12 R 0 to 1,700 (°C)
/0 to 3,000 (°F)
13 S 0 to 1,700 (°C)
/0 to 3,000 (°F)
14 B 100 to 1,800 (°C)
/300 to 3,200 (°F)
15 W 0 to 2,300 (°C)
/0 to 4,100 (°F)
16 PLII 0 to 1,300 (°C)
/0 to 2,300 (°F)
17 4 to 20 mA Current input
18 0 to 20 mA
19 1 to 5 V V oltage input
20 0 to 5 V
21 0 to 10 V
Parameter Initialize
Parameter initialization sets all parameters to default values except
for the input type, scaling upper limit, scaling lower limit, decimal
point, and °C/°F selection parameters.
E5AK E5AK
11
To previous page From previous page
Control output 1
assignment (Not
displayed by the
E5jK-PRR2)
Control output 2
assignment (Not
displayed by the
E5jK-PRR2)
Auxiliary output 1
assignment
Output
assignment
Auxiliary output 2
assignment
Alarm 1 type
Alarm 1
open in
alarm
Alarm 2 type Alarm type
Alarm 2
open in
alarm
Alarm
1, 2, or
3 is not
set.
Alarm 3 type
Alarm 3
open in
alarm
Direct/Reverse
operation
Output Assignments
Signals available as allocated outputs are the control output (heat),
control output (cool), alarm 1, alarm 2, alarm 3, LBA, and HBA. The
auxiliary outputs of the Digital Controller cannot be used as control
outputs.
Control output (heat), control output (cool) , alarm 1, alarm 2, alarm
3, LBA, error 1 (input error), error 2 (A/D converter error), and error 3
(RSP input error) output functions are available. These functions
are assigned to control outputs 1 and 2 and auxiliary outputs 1 and
2.
The assignment destination of each output function is may be re-
stricted. Refer to the following table.
Standard Models
Assignment
destination Control
output Auxiliary
output
destination
Output function 1 2 1 2
Control output (heat) Yes Yes --- ---
Control output (cool) Yes Yes --- ---
Alarm 1 Yes Yes Yes Yes
Alarm 2 Yes Yes Yes Yes
Alarm 3 Yes Yes Yes Yes
HBA Yes Yes Yes Yes
LBA Yes Yes Yes Yes
Error 1: Input error --- --- Yes Yes
Error 2: A/D converter error --- --- Yes Yes
Error 3: RSP input error --- --- Yes Yes
With control output (cool), the conditions for switching from
standard control to heating and cooling control are reached
when the output function is assigned at the cooling side during
heating and cooling control.
In other words, heating and cooling control is carried out when con-
trol output (cool) is assigned, and standard control is carried out
when output is not assigned.
Position-proportional Models
Assignment
destination Control
output Auxiliary
output
destination
Output function 1 2 1 2
Alarm 1 --- --- Yes Yes
Alarm 2 --- --- Yes Yes
Alarm 3 --- --- Yes Yes
Error 1: Input error --- --- Yes Yes
Error 2: A/D converter error --- --- Yes Yes
Error 3: RSP input error --- --- Yes Yes
LBA
The LBA (loop break alarm) function is available when it is assigned
as an output. The LBA function is not available when a memory or
A/D converter error results.
LBA is a function for determining that an error has occurred some-
where on the control loop and outputting an alarm when the process
value does not change with the manipulated variable at a maximum
or minimum state. Accordingly, the LBA function can be used as a
means for detecting a malfunctioning control loop.
E5AK E5AK
12
Alarm Mode Selectors
Alarm outputs are available if they are allocated as outputs. Factory setting is “2: Upper-limit alarm (deviation).”
Switch
setting
Alarm operation Alarm output
setting When X is positive When X is negative
1Upper- and lower-limit alarm (deviation) XX
ON
OFF SP
Always ON
2Upper-limit alarm (deviation) X
SP
ON
OFF
X
SP
ON
OFF
3Lower-limit alarm (deviation) X
SP
ON
OFF
X
SP
ON
OFF
4Upper- and lower-limit range alarm (deviation) XX
SP
ON
OFF
Always OFF
5Upper- and lower-limit alarm with standby se-
quence (deviation) XX
SP
ON
OFF
Always OFF
6Upper-limit alarm with standby sequence
(deviation) X
SP
ON
OFF
X
SP
ON
OFF
7Lower-limit alarm with standby sequence
(deviation) X
SP
ON
OFF
X
SP
ON
OFF
8Absolute-value upper-limit alarm X
0
ON
OFF 0
X
ON
OFF
9Absolute-value lower-limit alarm X
0
ON
OFF 0
X
ON
OFF
10 Absolute-value upper-limit alarm with standby
sequence X
0
ON
OFF 0
X
ON
OFF
11 Absolute-value lower-limit alarm with standby
sequence X
0
ON
OFF 0
X
ON
OFF
Deviation Alarm
If the alarm mode selector is set to a number between 1 to 7, alarm
values are set to the width deviated from the set point as shown in
the following illustration.
Set point (SP)
100°C/°F
Alarm value
10°C/°F
110°C/°F
Absolute Alarm
If the alarm mode selector is set to 8 or 9, alarm values are set to the
absolute value based on 0°C/°F as shown in the following illustra-
tion.
0°C/°F
Alarm value
110°C/°F
110°C/°F
When selecting a control method, refer to the following table for cor-
rect parameter setting.
Control
method Control
output 1
assignment
Control
output 2
assignment
Operation
Heat Control
output (heat) --- Reverse
Cool Control
output (heat) --- Direct
Heat/Cool Control
output (heat) Control
output (cool) Reverse
E5AK E5AK
13
Close in Alarm/Open in Alarm
When the Controller is set to “close in alarm,” the status of the alarm
output function is output as it is. When set to “open in alarm,” the sta-
tus of the alarm output function is output inverted.
Condition Alarm Output Output LED
Close in
l
ON ON Lit
alarm OFF OFF Not lit
Open in
l
ON OFF Lit
alarm OFF ON Not lit
Alarm type and close in alarm (normally open)/open in alarm (nor-
mally close) can be set independently from each alarm.
Close in alarm/Open in alarm is set in the “alarm 1 to 3 open in
alarm” parameters (setup mode). Factory setting is “close in alarm”
[ n-o ].
Parameter Operation List
Switching to modes other than manual or protect mode is carried out using the mode selection in the menu display.
The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode
setting and conditions of use.
A/M
A/M
A/M
A/M
A/M
++
+
1 second min. Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
1 second min. Manual mode
Protect mode
1 second min.
1 second min. 1 second min.
1 second min.
Parameters in a mode can be
switched by the Display Key. The
parameter following the last param-
eter is the top parameter.
1 second min.
Note: The control of the Digital Controller is reset when the Digital Controller is in setup, expansion, option,
or calibration mode, in which case the control and auxiliary outputs are OFF . The reset condition will
be canceled when the Digital Controller is in any mode other than the above.
Power ON
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Parameters and Menus
Note: For more details on the functions of each part and display contents, refer to the
E5AK/E5EK User’s Manual (H83/H85)
.
All functions selected with the Digital Controller in setup or expansion mode or all optional functions of the Digital Controller may not be
displayed.
Protect Mode Limits use of the menu and A/M Keys. The protect function prevents unwanted modification of pa-
rameters and switching between the auto and manual operation.
Manual Mode The Controller can be switched to manual operation. The manipulated variable can be manipulated
manually only in this mode.
Level 0 Mode Set the Controller to this mode during normal operation. In this mode, change the set point during
operation, and start or stop Controller operation. The process value, ramp SP, and manipulated vari-
able can only be monitored in this mode.
E5AK E5AK
14
Level 1 Mode The main mode for adjusting control. In this mode, execute A T (auto-tuning), and set alarm values,
the control period, and PID parameters.
Level 2 Mode The auxiliary mode for adjusting control. In this mode, set the parameters for limiting the manipulated
variable and set point, switch between the remote and local modes, switch between the SP mode,
and set the loop break alarm (LBA), alarm hysteresis, and the digital filter value of inputs.
Setup Mode The mode for setting the basic specifications. In this mode, set parameters that must be checked or
set before operation such as the input type, scaling, output assignments and direct/reverse opera-
tion.
Expansion Mode The mode for setting expanded functions. In this mode, set ST (self-tuning), SP setting limiter, select
advanced PID or ON/OFF control, specify the standby sequence resetting method, and set the time
for automatic return to the monitoring display.
Option Mode The mode for setting option functions. Select this mode only when the Option Unit is set in the Con-
troller . In this mode, set the communications conditions, transfer output and event input parameters
to match the type of Option Unit set in the Controller . Heater burnout latch function, position-propor-
tional travel time, and remote SP scaling parameter are also located in this mode.
Calibration Mode The mode for calibrating inputs and transfer output.
When calibrating input, the selected input type is calibrated. Whereas, transfer output can be cali-
brated only when the Communications Unit (E53-CKF) is set in the Controller.
Parameter Operation
Refer to the
E5AK/E5EK User’s Manual (H83/H85)
for each parameter and the calibration mode in detail.
Refer to page 7 for the setting in detail.
Level 0 Mode
Process value PV/SV (local SP/remote SP)
Set point during SP ramp
For E5jK-PRR2
Manipulated
variable
MV monitor (heat) Valve opening
monitor
(Heat/Cool)
MV monitor
(cool)
Run/Stop
Manipulated
variable
PV/SV
The process value is displayed on the No.1 display and the set point
is displayed on the No.2 display.
When the multi-SP function is in use, the value of whichever is set,
set point 0 or 1, is linked.
Remote SP Monitor
Monitors remote SP in the local SP mode.
Set Point During SP Ramp
Monitors the set point when the SP ramp function is used.
SP Ramp
With the SP ramp function, the Controller operates according to the
value (set point during SP ramp) limited by a change rate, instead of
the changed set point when the set point is changed. The interval in
which the set point during SP ramp is limited is referred to as the “SP
ramp.”
Set point SP ramp
SP ramp
set value
SP ramp time unit
Switching point
Time
The change rate during the SP ramp is specified by the “SP ramp set
value” and “SP ramp time unit” parameters. At the “SP ramp set val-
ue” default “0,” the SP ramp function is disabled.
The set point changing in SP ramp can be monitored in the “Set
point during SP ramp” parameter (level 0 mode).
E5AK E5AK
15
Protect Mode
Press twice
for 1 s min.
Security
A/M Key protect
To level 0 Press twice
for 1 s min.
Security
Any mode marked with “X” in the following table is not displayed on
the menu when this parameter is set to “0” to “3.”
Mode Set value
0 1 2 3 4
Calibration --- x x x x
Option --- --- x x x
Expansion --- --- x x x
Setup --- --- x x x
Level 2 --- --- --- x x
Level 1, 0 --- --- --- --- x
The Unit will be in only level 0 mode and the menu will not be avail-
able when this parameter is set to “4” to “6.”
Only the “PV/SP” parameter in the level 0 mode can be used when
this parameter is set to “5.”
Only the “PV/SP” parameter in the level 0 mode can be used when
this parameter is set to “6.”
A/M Key Protect
Invalidate the function of the A/M Key.
Manual Mode
Process value
Manipulated variable/
Valve opening
MANU indicator
Bar graph (see note)
1 s min.
1 s min.
Note: Only for E5AK
E5AK E5AK
16
Level 1 Mode
AT Execute/Cancel
Set Point 0
Used with multi-SP function.
Set Point 1
Used with multi-SP function.
Set Point 2
Used with multi-SP function.
Set Point 3
Used with multi-SP function.
Alarm Value 1
Available only when the alarm output 1 is assigned.
Alarm Value 2
Available only when the alarm output 2 is assigned.
Alarm Value 3
Available only when the alarm output 3 is assigned.
Proportional Band
Available if the Controller is in advanced PID control.
Integral Time
Available if the Controller is in advanced PID control.
Derivative Time
Available if the Controller is in advanced PID control.
For heating/cooling control For E5jK-PRR2
Cooling Coefficient
Used with the Controller is in
heating and cooling control.
Dead Band
Used with the Controller is in
heating and cooling control.
Manual Reset Value
Available when the integral time parameter
of the Controller in standard control is “0”.
Hysteresis (Heat)
Available when the Controller is in
ON/OFF control.
For heating/cooling control
Hysteresis (Cool)
Available when the Controller is in
ON/OFF control
Control Period (Heat)
Available when the Controller has a relay or
voltage output, or is in advanced PID control.
For heating/cooling control
Control Period (Cool)
Available when the Controller has a relay
or voltage output, or is in advanced PID
control.
Current value Heater Current Monitor
Available when the heater
burnout alarm is assigned.
Heater Burnout Detection
Available when the heater
burnout alarm is assigned.
Position-
proportional
dead band
Level 2 Mode
Remote/Local
Used for the
communications function.
SP Mode
SP Ramp Time Unit
SP Ramp Set Value
LBA Detection Time
Available when the LBA (loop break
alarm) is assigned as an output.
Unavailable to the E5jK-PRR2.
MV at Stop
MV at PV Error
MV Upper Limit
Unavailable to the
E5jK-PRR2.
MV Lower Limit
Unavailable to the
E5jK-PRR2.
MV Change Rate Limit
Input Digital Filter
Alarm 1 Hysteresis
Available only when the alarm
output 1 is assigned.
Alarm 2 Hysteresis
Available only when the alarm
output 2 is assigned.
Alarm 3 Hysteresis
Available only when the alarm
output 3 is assigned.
Input Shift Upper Limit
Available if the input type is a
thermocouple or platinum resistance
thermometer.
Input Shift Lower Limit
Available if the input type is a
thermocouple or platinum resistance
thermometer.
(See
Input Shift
)
For E5jK-PRR2
Open/Close hysteresis
E5AK E5AK
17
Input Shift
When temperature input is selected, scaling is not required. This is
because input is treated as the “temperature” as it is matched to the
input type. However, note that the upper- and lower-limit values of
the sensor can be shifted. For example, if both the upper- and lower-
limit values are shifted by 1.2°C, the process value (before shift) is
regarded as 201.2°C after shift when input is 200°C before shift.
To set the input shift, set shift values in the “input shift upper limit”
and “input shift lower limit” parameters (level 2 mode).
Temperature
Upper limit
Upper-limit compensation value
After
compensation
Before compensation
Lower limit Lower-limit
compensation value Input (% of full scale)
Setup Mode
Input type
Temperature input Current/Voltage input
°C/°F
selection
Scaling
upper limit
Scaling
lower limit
Decimal point
Parameter initialize
Control output 1
assignment (Not
displayed by the
E5jK-PRR2)
Control output 2
assignment (Not
displayed by the
E5jK-PRR2)
Auxiliary output 1
assignment
Output
assignment
Auxiliary output 2
assignment
Alarm 1 type
Alarm 1
open in
alarm
Alarm 2 type
Alarm type
Alarm 2
open in
alarm
Alarm
1, 2, or
3 is not
set.
Alarm 3 type
Alarm 3
open in
alarm
Direct/Reverse
operation
E5AK E5AK
18
Expansion Mode
Set point
Upper Limit
Set point
Lower Limit
PID/ON/OFF
Unavailable to the
E5jK-PRR2.
ST
Available if the Controller in standard control and
advanced PID control has a temperature input.
Unavailable to the E5jK-PRR2
ST Stable Range
Available if the Controller in standard control and advanced
PID control with the ST set to OFF has a temperature input.
Unavailable to the E5jK-PRR2
α
Available if the Controller is in advanced
PID control with the ST set to OFF.
AT Calculated Gain
Available if the Controller is in advanced
PID control with the ST set to OFF.
Standby Sequence
Reset Method
Automatic Return
of Display Mode
AT Hysteresis
Available if the Controller is in advanced
PID control with the ST set to OFF.
LBA Detection Width
Available only when the LBA (loop break
alarm) function is assigned.
Unavailable to the E5jK-PRR2.
Option Mode
Multi-SP Function
Available for the event input functions.
Event Input Assignment 1
Available for the event input function.
Event Input Assignment 2
Available for the event input function.
Event Input Assignment 3
Available for the event input function.
Event Input Assignment 4
Available for the event input function.
Communication Stop Bit
Used when the communications function is being used.
Communication Data Length
Used when the communications function is being used.
Communication Parity
Set when the communications function is being used.
Communication Baud Rate
Set when the communications function is being used.
Communication Unit No.
Set when the communications function is being used.
Transfer Output Type
Set when the transfer output function is being used.
Transfer Output Upper Limit
Set when the transfer output function is being used.
Transfer Output Lower Limit
Set when the transfer output function is being used.
For E5jK-PRR2
Motor
calibration
Travel time
PV dead
band
HBA latch
Remote SP enable
Remote SP Upper
Limit
(Available when the
remote SP is enable.)
Remote SP Lower Limit
(Available when the remote SP is enable.)
SP tracking
(Available when the remote SP is enable.)
E5AK E5AK
19
How to Use the Error Display
When an error has occurred, the No.1 display alternately indicates error codes together with the current display item.
This section describes how to check error codes on the display, and the actions that must be taken to remedy the problem.
Input Error
Meaning Input is in error.
Action Check the wiring of inputs, disconnections, and shorts, and check the input type and the input type
jumper connector.
Operation at Error For control output functions, output the manipulated variable matched to the setting of the “MV at PV
error” parameter (level 2 mode). Alarm output functions are activated when the upper limit is exceed-
ed.
Memory Error
Meaning Internal memory operation is in error
Action First, turn the power OFF then back ON again. If the display remains the same, the E5AK/E5EK Con-
troller must be repaired. If the display is restored to normal, the probable cause may be external noise
affecting the control system. Check for external noise.
Operation at Error Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in
case of other outputs). Alarm output functions turn OFF.
A/D Converter Error
Meaning Internal circuits are in error.
Action First, turn the power OFF then back ON again. If the display remains the same, the E5AK/E5EK Con-
troller must be repaired. If the display is restored to normal, the probable cause may be external noise
affecting the control system. Check for external noise.
Operation at Error Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in
case of other outputs). Alarm output functions turn OFF.
Calibration Data Error
This error is output only during temperature input and is displayed for two seconds when the power is
turned ON.
Meaning Calibration data is in error.
Action Must repair.
Operation at Error Both control output functions and alarm output functions are active. However , note that the readout
accuracy is not assured.
Display Range Over
Meaning Though not an error, this is displayed when the process value exceeds the display range when the
control range (setting range ±10%) is larger than the display range (–1999 to 9999).
When less than “–1999”
When greater than “9999”
Operation Control continues, allowing normal operation.
E5AK E5AK
20
Motor Calibration Error (Displayed on the No. 2 Display)
Meaning Motor calibration has ended with an error.
Action First, correctly connect the wiring for the potentiometer, open output, and close output.
Execute the motor calibration again.
Operation Procedure
Operation at Error When motor calibration is executed, open output will operate and then close output will operate.
However, as the value is incorrect, the result turns out to be an error.
E5AK E5AK
21
Fuzzy Self-tuning
Fuzzy self-tuning is a function that enables the E5AK/E5EK to cal-
culate the most suitable PID constants for the controlled object.
Features
The E5AK/E5EK determines by itself when to perform fuzzy
self-tuning.
Fuzzy Self-tuning Function
The fuzzy self-tuning function has three modes.
In SRT (step response tuning) mode, the PID constants are tuned
using a step response method at the time the set point is changed.
In DT (disturbance tuning) mode, the PID constants are amended
so that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT (hunting tuning) mode, when hunting occurs, the PID
constants are amended to suppress the hunting.
Note: Be sure to turn on the power supply to the load either before
or simultaneously with the start of Temperature Controller
operation.
Dead time will be measured from the time the Temperature
Controller starts operating. If a load such as a heater is
turned on after the Temperature Controller is turned on,
dead time longer than the actual value will be measured
and inappropriate PID constants will be obtained. If an ex-
tremely large amount of dead time is measured, the control
amount will be set to 0% for a short period of time before
being returned to 100%, and the constants will then be re-
tuned. Retuning is performed only for large amounts of
dead time, so be sure to follow the precaution given above
when starting operation.
Startup Conditions of SRT
SRT will start if the following conditions are satisfied simultaneously
when the E5AK/E5EK is turned on or the set point is changed.
At the time the E5AK/E5EK
starts operating At the time set point is
changed
1. The set point at the time the
E5AK/E5EK starts operating
is different from the set point
used at the time SRT was last
executed (see note).
2. The process value at the time
the E5AK/E5EK starts operat-
ing is smaller than the set
point in reverse operation and
larger than the set point in
normal operation.
1. The new set point is
different from the set point
used at the time SRT was
last executed (see note).
2. The process value is in
stable condition before
the set point is changed.
3. A larger set point value is
set in reverse operation
and a smaller set point is
set in normal operation.
Note: The last SRT -executed set point is set to 0 before shipping
and when changing from advanced PID control to ad-
vanced PID control with fuzzy self-tuning.
PID Constant Refreshing Conditions
If the step control amount is applied before the maximum tempera-
ture slope (R) is obtained, SRT will not renew any PID constant. If
the proportional band obtained from the R and L values that were
measured before the imposition had been completed is larger than
the present proportional band, the PID constants will be renewed
because the measured value is in the direction towards the suitable
proportional band value, and the set point at that time will be the
SRT-executed set point.
Temperature Slope (R) Stable range
Time
SP
Stable Temperature Status
If the temperature is within the stable range for a certain time, it is
deemed that the temperature is stable. This time is called stability
judgement time. Like PID constants, stability judgement time is ad-
justed with fuzzy self-tuning according to the characteristics of the
object to be controlled. Fuzzy self-tuning will not be activated if the
temperature is stable because the Temperature Controller deems
that temperature control is smooth.
Shorter than the stability judgement time
Set
point
Stable
range
Stable
range
(Set to
15.0_C
before
shipping)
Stability judgement time
Stable Stable
Balanced Status
If the process value is within the stable range for 60 s when there is
no output, it is deemed that the the temperature is balanced.
Startup Conditions of DT
1. DT will start if the temperature that has been stable varies due
to external disturbance and the deflection of the temperature
exceeds the stable range, and then the temperature
becomes stable, provided that the number of maximum
temperature values is less than four.
2. DT will start if the set point is changed under the condition that
SRT does not start and the temperature becomes stable,
provided that the number of maximum temperature values is
less than four.
If there are four or more maximum temperature values, HT
will start.
SP
Temperature Extreme value 2 Set point change
Time
Extreme value 1
E5AK E5AK
22
Startup Conditions of HT
HT will be ON when there is hunting with four or more maximum
temperature values (extreme values) while SRT is not being execut-
ed.
Extreme value 2 Extreme value 4
Extreme
value 1 Extreme
value 3
Temperature
Time
SP
Note: In specific applications where temperature varies periodi-
cally due to disturbance, internal parameters need to be ad-
justed. For details, refer to the
E5AK/E5EK User’s Manual
(H83/H85)
.
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5AK
E5EK
Panel Cutouts
Note: 1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal
mounting space between each Unit. Units must
not be closely mounted vertically or horizontally .
Panel Cutouts
Note: 1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal
mounting space between each Unit. Units must
not be closely mounted vertically or horizontally.
96 x 96
91 x 91
110 min.
120 min.
120 min.
60 min.
E5AK E5AK
23
Accessories (Order Separately)
Terminal Cover
E53-COV0809 E53-COV08
Current Transformer
E54-CT1 E54-CT3
5.8 dia. 12 dia.
2.36 dia.
Two, M3 (depth: 4)
40x40
E5AK E5AK
24
Installation
Wiring Terminals for E5AK
Terminal Arrangement
TRSF: T ransfer output
EV1 to 4: Event input
PTMR: Potentiometer
RSP: Remote SP input
AC100–240V~
(AC/DC24V~)
SOURCE
Wiring
In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller.
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 9 and 10 according to the specifications.
Sensor Input
Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
E5AK E5AK
25
Control Output
Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following dia-
grams show the available Output Units and their internal equalizing circuits.
With E53-Vjj Output Units, approx. 2 V is output for one second after the power is interrupted.
The following table shows the specifications for each Output Unit.
Model Output type Specifications
E53-R Relay 5 A at 250 VAC
E53-S SSR 1 A at 75 to 250 VAC
E53-Q
E53-Q3
E53-Q4
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
E53-C3
E53-C3D 4 to 20 mA
0 to 20 mA 4 to 20 mA; permissible load impedance: 600 max.; resolution: approx. 2600
0 to 20 mA; permissible load impedance: 600 max.; resolution: approx. 2600
E53-V34
E53-V35 0 to 10 V
0 to 5 V 0 to 10 VDC; permissible load impedance: 1 k min.; resolution: approx. 2600
0 to 5 VDC; permissible load impedance: 1 k min.; resolution: approx. 2600
With E5AK-PRR2 Controllers, the relay output (1 A at 250 VAC) is fixed.
When replacing the Output Unit, use the E53-R. The following diagrams show the relationship between terminals and open/close relay set-
tings.
8
7
Open
6
5
Close
Auxiliary Output
Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The following
diagrams show the internal equalizing circuits for the auxiliary outputs:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
4
3
2
1
Auxiliary
output 1 Auxiliary
output 2
Output specifications are as follows:
SPST-NO, 3 A at 250 VAC
E5AK E5AK
26
CT Input/Potentiometer
When using the HBA function on the E5AK-AA2 Controller, connect CT input (CT) to terminal numbers 15 to 17. When monitoring the valve
opening on the E5AK-PRR2 Controller, connect the potentiometer (PTMR) to terminal numbers 15 to 17. Connect each of these inputs as
follows:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
17
16
15
17
16
15 C
W
O
CT
CT input Potentiometer
For details on CT inputs, refer to
Appendix, About Current T ransformer
in the
E5AK/E5EK User’s Manual (H83/H85)
. For details on the poten-
tiometer, refer to the
Instruction Manual
for the valve connected to the Controller. The variable resistance range is 100 to 2.5 k.
Remote SP Input
Connect the input (RSP) to be used as the remote SP to terminal numbers 21 and 22. Only 4 to 20 mA inputs can be connected. Connect the
input as follows:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
21
+
22 4 to 20 mA
E5AK E5AK
27
Event Input
Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20, and event events 3 and 4 (EV3/4) to terminal numbers 24 to 26. However ,
note that terminal numbers 18 to 20 cannot be used on Controllers with a communications function. Connect the event inputs as follows:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
20
19
18
26
25
24
+
+
Event input 1 and 2 Event input 3 and 4
EV1
EV2
COM
EV3
EV4
COM
+
+
Terminals 18 and 24 (COM) are connected internally.
Use event inputs under the following conditions:
Contact input ON: 1 k max.
OFF: 100 k min.
No-contact input ON: Residual voltage 1.5 V max.,
OFF: Leakage current 0.1 mA max.
Polarities during no-contact input are as follows:
20
19
18
26
25
24
+
+
Event input 1 and 2 Event input 3 and 4
EV1
EV2
COM
EV3
EV4
COM
+
+
Transfer Output
Connect transfer output (TRSF) to terminal numbers 29 and 30. The internal equalizing circuit for transfer output is as follows:
30
29
4 to 20mA L
+
T ransfer output specifications are as follows: 4 to 20 mA,
Permissible load impedance: 600 max.,
Resolution: Approx. 2600
Communications
Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with Communications Units (E53-AK01/02/03). For details on wiring,
refer to
Chapter 6, Using the Communications Function
in the
E5AK/E5EK User’s Manual (H83/H85)
.
E5AK E5AK
28
Wiring Terminals for E5EK
Terminal Arrangement
TRSF: T ransfer output
EV1/2: Event input
PTMR: Potentiometer
RSP: Remote SP input
AC100–240V~
(AC/DC24V~)
SOURCE
Wiring
In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller.
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 9 and 10 according to the specifications.
Sensor Input
Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
E5AK E5AK
29
Control Output
Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following dia-
grams show the available Output Units and their internal equalizing circuits.
With E53-Vjj Output Units, approx. 2 V is output for one second after the power is interrupted.
The following table shows the specifications for each Output Unit.
Model Output type Specifications
E53-R Relay 5 A at 250 VAC
E53-S SSR 1 A at 75 to 250 VAC
E53-Q
E53-Q3
E53-Q4
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
E53-C3
E53-C3D 4 to 20 mA
0 to 20 mA 4 to 20 mA, permissible load impedance: 600 max., resolution: approx. 2600
0 to 20 mA, permissible load impedance: 600 max., resolution: approx. 2600
E53-V34
E53-V35 0 to 10 V
0 to 5 V 0 to 10 VDC, permissible load impedance:1 k min., resolution: approx. 2600
0 to 5 VDC, permissible load impedance: 1 k min., resolution: approx. 2600
With E5EK-PRR2 Controllers, the relay output (1 A at 250 VAC) is fixed.
When replacing the Output Unit, use the E53-R. The following diagrams show the relationship between terminals and open/close relay set-
tings.
8
7
Open
6
5
Close
Auxiliary Output
Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The following
diagrams show the internal equalizing circuits for the auxiliary outputs:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
42
1
Auxiliary
output 1 Auxiliary
output 2
Output specifications are as follows:
SPST-NO, 3A at 250 VAC
E5AK E5AK
30
CT Input/Potentiometer
When using the HBA function on the E5EK-AA2 Controller, connect CT input (CT) to terminal numbers 15 to 17. When monitoring the valve
opening on the E5EK-PRR2 Controller, connect the potentiometer (PTMR) to terminal numbers 15 to 17. Connect each of these inputs as
follows:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
17
16
15
17
16
15
O
W
C
CT input Potentiometer
For details on CT inputs, refer to
Appendix, About Current T ransformer
in the
E5AK/E5EK User’s Manual (H83/H85)
. For details on the poten-
tiometer, refer to the
Instruction Manual
for the valve connected to the Controller. The variable resistance range is 100 to 2.5 k.
Remote SP Input
Connect the input (RSP) to be used as the remote SP to terminal numbers 15 and 16. However , note that the remote SP cannot be used on the
E5EK-PRR2 Controller. Only 4 to 20 mA inputs can be connected. Connect the input as follows:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
15
+
16 4 to 20 mA
Event Input
Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20. However , note that terminal numbers 18 to 20 cannot be used on Control-
lers with a communications function. Connect the event inputs as follows:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
20
19
18
Event input 1 and 2
EV1
EV2
COM
+
+
Use event inputs under the following conditions:
Contact input ON: 1 k max., OFF: 100 k min.
No-contact input ON: Residual voltage 1.5 V max.,
OFF: Leakage current 0.1 mA max.
E5AK E5AK
31
Polarities during no-contact input are as follows:
20
19
18
Event input 1 and 2
EV1
EV2
COM
+
+
Transfer Output
Connect transfer output (TRSF) to terminal numbers 21 and 22. The internal equalizing circuit for transfer output is as follows:
21
22
4 to 20mA L
+
T ransfer output specifications are as follows:4 to 20 mA,
Permissible load impedance: 600 max.,
Resolution: Approx. 2600
Communications
T erminal numbers 18 to 22 can be used only on controllers with Communications Units (E53-AK01/02/03). For details on wiring, refer to
Chap-
ter 6, Using the Communications Function
in the
E5AK/E5EK User’s Manual (H83/H85)
.
Precautions when Wiring
Use ducts to separate input leads and power lines in order to protect the Controller and its lines from external noise.
Solderless terminals are recommended when wiring the Controller.
Tighten the terminal screws using a torque no greater than 0.78 N S m, or 8 kgf S cm max. Take care not to tighten the terminal screws too tightly.
Power Blocks
The E5AK/E5EK has independent power supplies for each of the terminal blocks shown below.
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
AB C
B
FD
C
E
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
A B/C C
B
FD
E
E5AK E5EK
Note: Terminals 21 and 22 of the E5EK belong to the B block
when a transfer output is set to option 1 and to the C block
for other Option Units.
E5AK E5AK
32
Precautions
General Precautions
Operating Environment
Keep within the rated ambient operating temperature, ambient op-
erating humidity, and storage temperature ranges.
Use the Unit according to the vibration resistance, shock resist-
ance, and enclosure ratings.
Do not use the Unit in places with corrosive gas or excessive dust.
Do not use the Unit nearby machines generating high-frequency
noise.
Correct Use
Mounting
The dimensions of the Digital Controller conform to DIN 43700.
Recommended panel thickness is 1 to 8 mm.
Mount the Unit horizontally.
Connection
To reduce inductive noise influence, the lead wires connecting the
input type to the Digital Controller must be separated from the power
lines and load lines.
Use the specified compensating conductors for thermocouples.
Use lead wires having a small resistance for platinum resistance
thermometers.
Connection Example
Wire the terminals of the Unit using solderless terminals.
The tightening torque applied to the terminal screws of the Unit must
be approximately 0.78 N S m or 8 kgf S cm.
Use the following type of solderless terminals for M3.5 screws.
7.2 mm max.
7.2 mm max.
Operation
The alarm outputs of a model with an alarm function may not turn
ON properly when the model malfunctions. The use of alarm equip-
ment with the model is recommended.
The parameters and internal switch are set before shipping so that
the Unit will function normally. Change the settings of the parame-
ters and internal switch according to the application if necessary.
Several seconds are required until the relay is turned ON after pow-
er has been supplied to the Digital Controller. Therefore, take this
time delay into consideration when designing sequenced circuits
which incorporate a Digital Controller.
Do not use excessive force when drawing out the internal mecha-
nism from the housing. Protect the internal connector or electronic
parts of the Unit from shock. Protect against static discharge when
changing the settings of the internal switch. Changing the settings
on a grounded conductive mat is recommended.
When connecting the Control Output Unit to the Temperature Con-
troller or Digital Controller , make sure that the Control Output Unit is
a suitable type. The use of an improper type of Control Output Unit
may cause the system to malfunction.
The heater burnout alarm will not be available if the Linear Output
Unit is used.
E5AK E5AK
33
Period and Scope of Guarantee
Unit with Standard Specifications
Scope of Guarantee
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
1. Any malfunction of the Unit due to the incorrect use or
improper handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
Three-year Guarantee
Period of Guarantee
The guarantee period of the Unit is three years starting from the date
the Unit is shipped from the factory.
Scope of Guarantee
The Unit is guaranteed under the following operating conditions.
1. Average Operating Temperature (see note): –10°C to 50°C
2. Mounting Method: Standard mounting
Top
Bottom
Note: Average Operating Temperature
Refer to the process temperature of the Unit mounted to a
control panel and connected to peripheral devices on con-
dition that the Unit is in stable operation, sensor input type K
is selected for the Unit, the positive and negative thermo-
couple input terminals of the Unit are short-circuited, and
the ambient temperature is stable.
Should the Unit malfunction during the guarantee period, OMRON
shall repair the Unit or replace any parts of the Unit at the expense of
OMRON.
The above does not apply in the following cases.
1. Any malfunction of the Unit due to the incorrect use or
improper handling of the Unit.
2. Any malfunction of the Unit not originating from the Unit.
3. Any malfunction of the Unit due to a modification of the Unit or
repairs to the Unit carried out by any person not authorized by
OMRON.
4. Any malfunction of the Unit due to any natural disaster.
OMRON shall not be responsible for any damage or loss induced by
any malfunction of the Unit.
E5AK E5AK
34
SSR
Connection Example of Digital Controller and SSR
+
+
Digital Controller
Voltage output
terminal (for driv-
ing SSR)
Connectable
Load
Heater Power supply
for load
Power SSR
SSR
E5AK/E5EK
Digital Controller with
Voltage Output
(12 VDC, 40 mA max.)
See the following table.
E5CK
Digital Controller with
Voltage Output
(12 VDC, 20 mA max.)
INPUT LOAD
Model G3PA G3NH G3NA G3NE G3B
Appearance
SSRs connected
in parallel E5AK/E5EK:8 pcs.
E5CK: 4 pcs. E5AK/E5EK:8 pcs.
E5CK: 4 pcs. E5AK/E5EK:5 pcs.
E5CK: 2 pcs. E5AK/E5EK:2 pcs.
E5CK: 1 piece E5AK/E5EK:5 pcs.
E5CK: 2 pcs.
Rated input
voltage 5 to 24 VDC 5 to 24 VDC 5 to 24 VDC 12 VDC 5 to 24 VDC
Features Thin, monoblock
construction with
heat sink
For high-power
heater control Standard model with
screw terminals Compact, low-cost
model with tab
terminals
Socket, model with
5-A switching
capacity